HW serie bag filter

HW Serie Bag Filter is used as a prefilter or fine filter.
The filters are available in filter classes ePM1 50%, ePM1 85% in compliance with ISO 16890

  • Frame : Galvanized steel /Aluminium
  • Medium : Nanowave synthetic filter media
  • Gasket : Optional continuous poured gasket

eurovent

Filter class according to ISO 16890
ePM1
Energy label
B, C
Maximum final pressure drop
450Pa
home ventilation

HVAC

Industry

Industry

Specifications

  • Frame : Galvanized steel /Aluminium
  • Medium : Nanowave synthetic filter media
  • Gasket : Optional continuous poured gasket
  • Maximum temperature : 70 °C
  • Maximum relative humidity : 90%

Installation

  • Ensure that the filter is fitted correctly: Suction side – clean air side
  • Filter should be correctly installed: no leaks
  • Gaskets should be completely undamaged
  • Filter should be secured at four points
  • Make sure that the filter medium is not folded double
  • Take care to avoid damaging the filter during installation
  • System should be run in for several hours to achieve the desired result
  • Filter installation records; note the date, type and initial resistance
HW

Pressure drop