Synthetic medium
Construction
Our filter media are supplied either on a roll or in pre-cut sheets
Application
Pre-filters for air treatment systems. Pre-filters for spray-painting booths.
Specifications
Application: prefilters in HVAC and industry
Materiaal: polyester
Filterclass according to EN779:2002: G2, G3, G4, F5
Maximum final presssure drop: 250Pa
Maximum temperature: 70°C
Maximum relative humidity: 90%
Installation
- Ensure that the filter medium is fitted correctly
(fine side – dirty air side) - Ensure that the medium is installed flat
- Filter medium should be properly secured to prevent it from becoming dislodged or possibly leaking during its service life
- Filter installation records; note the date, type and initial resistance.