Activated carbon panel
Construction
Compact or HPQ filters are mini-pleat filters, which are assembled inside a polystyrene frame. This type of air filters is resistant to temperatures of up to 70°C.
Application
Compact or HPQ filters are used in air treatment cabinets, air conditioning systems, industrial systems and as a pre-filter in cleanrooms.
Specifications
Application: museums, archives, industry
Frame: galvanized steel
Bonding: 2 component polyurethane
Carbon: M-carb generic activated carbon. S-carb specific
impregnated carbon used for museums and archives
Gasket: Neopreen
Maximum/recommended final presssure drop: n.a.
Maximum temperature: 40°C
Maximum relative humidity: 70%
This activated carbon filter is designed to adsorb small amounts of gaseous impurities (<100 ppm vol.) At higher concentrations, a risk of spontaneous creation. For instructions on using these filters, refer to enclosed installation and maintenance instructions.
Installation
- Ensure that the filter is fitted correctly:
Suction side – clean air side - Filter should be correctly installed: no leaks
- Gaskets should be completely undamaged
- Filter should be secured at four points
- Ensure that the filter medium is not folded double
- Take care to avoid damaging the filter during installation
- System should be run in for several hours to achieve the desired result
- Filter installation records; note the date, type and initial resistance.